What are the requirements to obtain a simplified fire permit?
Applicable for limited-scope projects per FSS 553.7932
This permit is valid for alterations involving:
20 or fewer sprinklers with the same K-factor
Installation/replacement of equivalent system components in an existing commercial, residential, apartment, cooperative, or condominium building
⚠️ The project must not alter hazard classification or increase system coverage area.
“Component” includes: Valves, sprinklers, escutcheons, hangers, compressors, or similar items (excluding pressure-regulating/reducing/control valves)
📝 Plans:
Not required for qualifying projects
However, contractor must maintain plans, specifications, and permit on-site for inspector review
Include manufacturer's installation/testing instructions for component replacements
This permit applies only to:
Alterations of 20 or fewer initiating/notification devices
Installation/replacement of a fire communicator on an existing fire alarm control panel
📝 Plans:
Not required for qualifying projects
Contractor must maintain plans and permit at the worksite for inspection
For work over $5,000, documentation must be dated, signed, and sealed by a Florida-registered Professional Engineer
📌 Projects not meeting FSS 553.7932 criteria will require a standard fire alarm system permit.